Huawei LUNA2000-215-2S10 — capacity and round-trip efficiency test
Photomate · Business Center Residence · Kyiv · 23 June 2026
STANDARD IEC 62933-2-1:2017 ESS 215 kWh / 108 kW TEST POWER 54 kW · 0.25C RTE 92.04%
01 - Test objective and methodology
The test was performed using an independent measurement approach: the main charge and discharge parameters were measured by a separate external Metrel Power Master MI 2892 power quality analyzer at the ESS AC connection point. Data from the Huawei monitoring system were used for supplementary parameters such as SOC and temperature, while auxiliary consumption data were obtained from the ESS built-in auxiliary consumption meter. This approach allows the energy performance to be evaluated from independent measurements rather than relying solely on the ESS internal monitoring data.
The test was performed in accordance with IEC 62933-2-1:2017, which defines unit parameters and testing methods for electrical energy storage systems. The objective was to determine the usable AC energy delivered by the ESS and its round-trip efficiency during a complete charge/discharge cycle.
| Step | Procedure |
|---|---|
| 1 | Discharge the ESS to 0% SOC. |
| 2 | Charge from 0% to 100% SOC at 54 kW (0.25C), recording AC charge energy and auxiliary consumption. |
| 3 | Short stabilization pause. |
| 4 | Discharge from 100% to 0% SOC at 54 kW (0.25C), recording AC discharge energy and auxiliary consumption. |
02 - Test results
Charge phase
| Duration | 04:13:35 |
| Average power | 53.42 kW |
| Maximum power | 53.87 kW |
| Auxiliary consumption | 2.06 kWh |
Discharge phase
| Duration | 03:53:58 |
| Average power | 54.20 kW |
| Maximum power | 54.32 kW |
| Auxiliary consumption | 1.66 kWh |
03 - Complete charge/discharge cycle
Charge/discharge power measured by the Metrel analyzer is shown together with SOC from the ESS monitoring system. SOC was recorded at 5-minute intervals; the line between measured points is linearly interpolated for visualization.
Power and SOC profile
Left axis: kW · right axis: SOC %Thermal behavior during the cycle
Measured by the ESS monitoring systemThe chart shows the ESS air intake temperature and the highest/lowest battery-pack temperatures. The narrow pack-temperature band demonstrates stable thermal management during the full 0.25C cycle.
04 - Energy balance and efficiency
Cumulative AC energy
RTE calculation
RTE₁ = E D / E C × 100% = 93.61%
RTE₂ = (E D − W D ) / (E C + W C ) × 100% = 92.04%
| Parameter | Measured value |
|---|---|
| E C — energy supplied to the ESS during charge | 225.775 kWh |
| E D — energy delivered by the ESS during discharge | 211.355 kWh |
| W C — auxiliary consumption during charge | 2.06 kWh |
| W D — auxiliary consumption during discharge | 1.66 kWh |
05 - Auxiliary consumption
Auxiliary energy is taken from the ESS monitoring system's cumulative daily counter. Consumption for each phase is calculated as the difference between the counter values at the end and at the beginning of that phase.
06 - Test object and measurement equipment
Energy storage system
| Model | LUNA2000-215-2S10 |
| Rated power | 108 kW |
| Rated energy | 215 kWh |
| Serial number | P02512000881 |
| Manufacture date | 06.01.2025 |
| Commissioning date | 03.06.2026 |
| Software package | LUNA2000B_V200R024C00SPC415 |
Measurement equipment
| Power quality analyzer | Metrel Power Master MI 2892 |
| Analyzer serial number | SN 24141272 |
| Current clamps | A 1502 · 3000/300/30 A / 1V |
| Clamp serial numbers | 24142020 · 24122010 24142033 · 24142024 |
| Last verification | 09.2025 |